Features
Charger for lead-acid batteries(Flooded, Gel and AGM) and Li-ion batteries(lithium iron and lithium manganese)
Built-in default 3 stage charging curves and programmable curve
Built-in I2C interface, PMBus protocol(optional CANBus protocol)
Universal AC input / Full range (withstand 200VAC surge input for 5 seconds)
Built-in active PFC function
Forced air cooling by built-in DC fan
Output voltage and current programmable
Built-in OR-ing FET
Active current sharing up to 4800W(2+1)
Protection: Battery under voltage / Battery no connection / Short circuit / Over voltage / Over temperature
Optional conformal coating
5 years warranty
RPB-1600
MODEL | RPB-1600-12 | RPB-1600-24 | RPB-1600-48 |
---|
OUTPUT | BOOST CHARGE VOLTAGE Vboost | 14.4V | 28.8V | 57.6V |
FLOAT CHARGE VOLTAGE Vfloat | 13.8V | 27.6V | 55.2V |
CONSTANT CURRENT(CC)(default) | 100A | 55A | 27.5A |
VOLTAGE ADJ. RANGE | By built-in potentiometer, SVR |
11.5 ~ 15.1V | 23 ~ 30.2V | 46.1 ~ 60.5V |
RECOMMENDED BATTERY CAPACITY(AMP HOURS) | 330 ~ 1000Ah | 180 ~ 550Ah | 90 ~ 270AH |
LEAKAGE CURRENT FROM BATTERY | <1mA | <1mA | <1mA |
INPUT | VOLTAGE RANGE | 90 ~ 264VAC 127 ~ 370VDC |
FREQUENCY RANGE | 47 ~ 63Hz | 47 ~ 63Hz | 47 ~ 63Hz |
POWER FACTOR (Typ.) | 0.97/230VAC at full load |
EFFICIENCY (Typ.) | 91% | 92.5% | 93.5% |
AC CURRENT (Typ.) | 14A/115VAC 8A/230VAC | 15A/115VAC 8.5A/230VAC |
INRUSH CURRENT (Typ.) | COLD START 35A/230VAC |
LEAKAGE CURRENT | <3.5mA/ 240VAC | <3.5mA/ 240VAC | <3.5mA/ 240VAC |
|
|
|
|